Datasheet

https://www.phoenixcontact.com/us/produkte/2924016
Nov 14, 20133/7
Power/input isolating amplifier-MACX MCR-EX-SL-RPSSI-I-
SP-2924016
Technical data
General
Inflammability class according to UL 94
V0
Pollution degree
2
Surge voltage category
II
Housing material
PA 66-FR
Color
green
Name
Input/output/power supply
Electrical isolation
300 V
rms
(Rated insulation voltage (surge voltage category II;
pollution degree 2, safe isolation as per EN 61010-1))
Electrical isolation
2.5 kV (50 Hz, 1 min., test voltage)
Name
Input/output
Electrical isolation
375 V (Peak value in accordance with EN 60079-11)
Name
Input/power supply
Electrical isolation
375 V (Peak value in accordance with EN 60079-11)
Conformance
CE-compliant, additionally EN 61326
ATEX
 II (1) G [Ex ia Ga] IIC/IIB
ATEX
 II (1) D [Ex ia Da] IIIC
ATEX
 II 3 (1) G Ex nA [ia Ga] IIC/IIB T4 Gc
IECEx
[Ex ia Ga] IIC/IIB
IECEx
[Ex ia Da] IIIC
IECEx
Ex nA [ia Ga] IIC/IIB T4 Gc
UL, USA / Canada
Class I Div 2; IS for Class I, II, III Div 1
Functional safety (SIL)
SIL 2 according to EN 61508
Data communication (bypass)
HART function
Yes
Protocols supported
HART
Safety characteristic data
Integrity requirement
IEC 61508 - Low demand
Equipment type
Type A
Safety Integrity Level (SIL)
Up to 2
Safe Failure Fraction (SFF)
90.7 %
λ
SU
4.867 x 10
-7
(486.7 FIT)
λ
SD
0
λ
DU
5 x 10
-8
(50 FIT)
λ
DD
0
Probability of a hazardous failure on demand (PFD
AVG
)
2.19 x 10
-4
(1 year)
Probability of a hazardous failure on demand (PFD
AVG
)
8.76 x 10
-4
( years)
Probability of a hazardous failure on demand (PFD
AVG
)
1.1 x 10
-3
(5 years)
Diagnostic coverage (DC)
(DC
S
= 0%, DC
D
= 0%)
Integrity requirement
IEC 61508 - High demand