Measuring instrument-EEM-MB370-2907954
Technical data
Input data
Input name Voltage measuring input V1, V2, V3
Input voltage range 35 VAC ... 690 VAC (Phase/Phase)
20 VAC ... 400 VAC (Phase/neutral conductor)
60 VAC ... 2000000 VAC (primary)
60 VAC ... 400 VAC (secondary)
Surge voltage capacity 760 VAC (Phase/Phase)
Precision 0.2 %
Input name Current measurement I1, I2, I3
Input current 1 A (secondary)
5 A (secondary)
Current measuring range 1 A ... 20000 A (primary)
Overload capacity
6 A (I
max
)
Response threshold from measuring range nominal value 10 mA (1A)
Precision 0.2 %
Current overload 50 A for 1 s
Precision 0.5 %
Active energy (IEC 62053-22) Class 0.5S
Reactive power (IEC 62053-23) Class 2
Description of the input Digital input in accordance with IEC/EN61131-2 (type 3)
Number 1
Voltage input signal 0 VDC ... 30 VDC
Current input signal 2 mA ... 15 mA
Output data
Output description Digital output in accordance with IEC/EN61131-2 (type 3)
Number 1
Current output signal ≤ 100 mA
Device interface
Designation Network interface
Communication protocol Modbus/TCP
REST
Connection method RJ45
General
Supply voltage range 100 VAC ... 230 VAC (±20%)
150 VDC ... 250 VDC (±20%)
Power consumption ≤ 4 W
Mains type 3-phase (3 or 4-wire), 2-phase (2-wire), and single-phase (1-wire)
Color gray
Conformance CE-compliant
Test voltage 4 kV AC (50 Hz, 1 min.)