Data Sheet

https://www.phoenixcontact.com/us/products/2906231
May 3, 20172/4
Current transformer-PACT RCP-4000A-UIRO-D95-2906231
Technical data
Measuring transducer signal output
Current output signal
0 mA ... 21 mA (Can be set via software)
Voltage output signal
0 V ... 10 V (via DIP switch)
Voltage output signal
2 V ... 10 V (via DIP switch)
Voltage output signal
0 V ... 5 V (via DIP switch)
Voltage output signal
1 V ... 5 V (via DIP switch)
Voltage output signal
0 V ... 10.5 V (Can be set via software)
Load/output load current output
≤ 600 Ω (20 mA)
General data, measuring coil
Length of measuring coil
300 mm
Diameter of measuring coil
8.3 mm ±0.2 mm
Length of signal cable
3000 mm
Conductor structure signal line
2x 0.22 mm (Signal (tinned))
Conductor structure signal line
1x 0.22 mm (Shielding (tinned))
Coil material
Elastollan
Housing material
PC
Insulation
double insulation
Rated insulation voltage
1000 V AC (rms CAT III)
Rated insulation voltage
600 V AC (rms CAT IV)
Test voltage
10.45 kV (DC / 1 min.)
Basic accuracy
<± 0.21 %
UL, USA/Canada
UL 61010 Recognized
General data for measuring transducer
Maximum transmission error
≤ 0.5 % (From the range end value)
Frequency range
16 Hz ... 1000 Hz
Housing material
PBT
Degree of protection
IP20
Test voltage
3 kV (50 Hz, 1 min.)
UL, USA/Canada
UL 508 Listed
General data
Standards/regulations
IEC61010-1
Standards/regulations
IEC61010-2-032
Degree of pollution
2
Overvoltage category
II
Typical measuring error
< 1 %
Connection data
Connection name
Measuring transducer side
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
1.5 mm²