Data Sheet

https://www.phoenixcontact.com/us/products/2904921
May 3, 20172/4
Current transformer-PACT RCP-4000A-1A-D95-2904921
Technical data
Measuring transducer signal output
Load
0 Ω ... 1.5 Ω
Operating voltage display
Green LED
General data, measuring coil
Length of measuring coil
300 mm
Diameter of measuring coil
8.3 mm ±0.2 mm
Length of signal cable
3000 mm
Conductor structure signal line
2x 0.22 mm (Signal (tinned))
Conductor structure signal line
1x 0.22 mm (Shielding (tinned))
Coil material
Elastollan
Housing material
PC
Insulation
double insulation
Rated insulation voltage
1000 V AC (rms CAT III)
Rated insulation voltage
600 V AC (rms CAT IV)
Test voltage
10.45 kV (DC / 1 min.)
Basic accuracy
<± 0.21 %
UL, USA/Canada
UL 61010 Recognized
General data for measuring transducer
Linearity error
< 0.5 % (From the range end value)
Maximum transmission error
≤ 0.5 % (From the range end value)
Frequency range
45 Hz ... 65 Hz
Current consumption
< 190 mA (at 19.2 V)
Housing material
Polyamide
Degree of protection
IP20
Test voltage
1.5 kV AC (Supply/input and output: 50 Hz, 1 min)
UL, USA/Canada
UL 508 Listed
General data
Standards/regulations
IEC61010-1
Standards/regulations
IEC61010-2-032
Insulation
double insulation
Degree of pollution
2
Overvoltage category
III (1,000 V, to neutral conductor)
Overvoltage category
IV (600 V, to neutral conductor)
Temperature coefficients
0.005 %/K (+10°C ... +70°C; both components have the same
ambient temperature)
Temperature coefficients
0.07 %/K (-20°C ... +10°C; both components have the same
ambient temperature)
Typical measuring error
< 1 %
Connection data
Connection name
Measuring transducer side
Conductor cross section flexible min.
0.2 mm²