Datasheet

https://www.phoenixcontact.com/gb/products/2904621
12/04/2018Page3/10
Power supply unit-QUINT4-PS/3AC/24DC/10-2904621
Technical data
Output data
Selective Fuse Breaking (I
SFB
)
60 A (15 ms)
Derating > 60 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes
Feedback resistance ≤ 35 V DC
Protection against surge voltage on the output ≤ 32 V DC
Control deviation < 0.5 % (Static load change 10% ... 90%)
< 2 % (Dynamic load change 10% ... 90%, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple
< 75 mV
PP
(with nominal values)
Output power 240 W
Typical response time 300 ms (from SLEEP MODE)
Maximum power dissipation in no-load condition < 5 W (400 V AC)
< 5 W (480 V AC)
Power loss nominal load max. < 19 W (400 V AC)
< 20 W (480 V AC)
General
Net weight 0.9 kg
Efficiency typ. 93 % (400 V AC)
typ. 92.6 % (480 V AC)
Insulation voltage input/output 4 kV AC (type test)
2.4 kV AC (routine test)
Insulation voltage input / PE 3.5 kV AC (type test)
2.4 kV AC (routine test)
Insulation voltage output / PE 0.5 kV DC (type test)
0.5 kV DC (routine test)
Protection class I
Degree of protection IP20
MTBF (IEC 61709, SN 29500) > 1034000 h (25 °C)
> 654000 h (40 °C)
> 320000 h (60 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions
alignable: P
N
≥50%, 5mm horizontally, 15mm next to active
components, 50mm vertically
alignable: P
N
<50%, 0mm horizontally, 40mm vertically top, 20 mm
vertically bottom
Connection data, input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section flexible min. 0.2 mm²