Datasheet

QUINT4-PS/3AC/24DC/5
107103_en_00 PHOENIX CONTACT 9 / 38
General data
Degree of protection IP20
Protection class I
Inflammability class in acc. with UL 94 (housing) V0
Side element version Aluminum
Hood version Stainless steel X6Cr17
Weight 0.6 kg
Power dissipation 400 V AC 480 V AC
Maximum power dissipation in no-load condition < 3 W < 4 W
Power dissipation SLEEP MODE < 3 W < 4 W
Power loss nominal load max. < 15 W < 17 W
Efficiency 400 V AC 480 V AC
typ. 89 % typ. 87.5 %
70
75
80
85
90
95
I [A]
Out
Eta [%]
= U : 400 V3AC/U : 24 VDC
In Out
= U : 480 V3AC/U : 24 VDC
In Out
12345678910
Ambient conditions
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
The ambient temperature (operation) refers to UL 508 surrounding air temperature.
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 95 % (at 25 °C, non-condensing)
Installation height 5000 m (> 2000 m, observe derating)
Vibration (operation) 5 Hz - 100 Hz resonance search 2.3g, 90 min., resonance
frequency 2.3g, 90 min. (according to DNV GL Class C)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-
2-27)
Degree of pollution 2
Climatic class 3K3 (in acc. with EN 60721)
Overvoltage category
EN 62477-1 III