Datasheet
UNO-PS/1AC/24DC/150W
106261_en_02 PHOENIX CONTACT 4
4 Technical data
Input data
Nominal input voltage 100 V AC ... 240 V AC
Input voltage range 85 V AC ... 264 V AC
AC frequency range 45 Hz ... 65 Hz
Current consumption 1.4 A (120 V AC)
0.8 A (230 V AC)
Inrush current limitation < 50 A (typical)
I
2
t < 0.8 A
2
s
Typical response time < 1 s
Power failure bypass > 20 ms (120 V AC)
> 20 ms (230 V AC)
Protective circuit Transient surge protection Varistor
Input fuse, integrated 2.5 A (slow-blow, internal)
Choice of suitable fuses 6 A ... 16 A (Characteristics B, C, D, K)
Input connection data
Connection method Screw connection
Conductor cross section, solid 0.2 mm² ... 2.5 mm²
Conductor cross section, stranded 0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil 24 ... 14
Stripping length 8 mm
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm
Output data
Nominal output voltage 24 V DC ±1%
Setting range of the output voltage 24 V DC ... 28 V DC ±1%
Output current 6.25 A (-25°C ... 55°C)
Derating 55 °C ... 70 °C (2.5%/K)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Rise time < 0.5 s (U
OUT
(10 % ... 90 %))
Residual ripple < 40 mV
PP
(with nominal values)
Connection in parallel yes, with redundancy module
Connection in series No
Protection against surge voltage on the output ≤ 35 V DC
Resistance to reverse feed < 35 V DC
Output connection data
Connection method Screw connection
Conductor cross section, solid 0.2 mm² ... 2.5 mm²
Conductor cross section, stranded 0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil 24 ... 14
Stripping length 8 mm
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm