Datasheet

UNO-PS/1AC/24DC/240W
106263_en_02 PHOENIX CONTACT 5
Power consumption
Efficiency > 93 % (for 230 V AC and nominal values)
Maximum power dissipation NO-Load < 1.1 W
Power loss nominal load max. < 18.8 W
General data
Insulation voltage input/output 4 kV AC (type test)
3 kV AC (routine test)
MTBF (IEC 61709, SN 29500) > 562000 h (40°C)
Housing material Aluminum / polycarbonate
Dimensions W/H/D 45 mm / 130 mm / 125 mm
Weight 0.66 kg
Security
Degree of protection IP20
Protection class I ( in closed control cabinet )
SELV EN 60950-1 (SELV) and EN 60204 (PELV)
Ambient conditions
Ambient temperature (operation) -25 °C ... 70 °C (> 55 °C Derating: 2,5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 95 % (at 25 °C, non-condensing)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Shock 30g in each direction, according to IEC 60068-2-27
Pollution degree 2
Climatic class 3K3 (in acc. with EN 60721)
Inflammability class in acc. with UL 94 (housing) V0
Standards
Electrical Equipment for Machinery EN 60204-1
Safety transformers for power supply units EN 61558-2-16
Electrical safety (of information technology equipment - Safety - Part 1) EN 60950-1/VDE 0805 (SELV)
Electronic equipment for use in electrical power installations EN 50178/VDE 0160 (PELV)
SELV EN 60950-1 (SELV) and EN 60204 (PELV)
Safe isolation DIN VDE 0100-410
Limitation of mains harmonic currents EN 61000-3-2
Network version/undervoltage EN61000-4-11
Information technology equipment - Safety (CBScheme) CB Scheme
Approvals
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950
Current approvals/permissions for the product can be found in the download area under phoenixcontact.net/products.