Datasheet

UNO-PS/1AC/24DC/240W
106263_en_02 PHOENIX CONTACT 17
10 Operating the power supply unit
10.1 Function monitoring
DC OK LED
The DC OK LED is available for visual function monitoring of the power supply unit.
Status 1 Status 2
DC OK LED lit OFF
Meaning Output voltage > 21.5 V Output voltage < 21.5 VDC, overload mode or no mains volt-
age
State description The device is operating, output voltage
and output current are OK
The device is in operation, but there is a fault on the side of
the consumer; the current consumption is greater than IN or
the output is short-circuited.
The device is out of operation because there is no mains
voltage, the fuse on the primary side has been triggered, or
the device is faulty.
Corrective Remove the error at the load, use a more powerful power
supply unit, connect a power supply unit of the same type
parallel to the existing device, remove the short circuit, apply
mains voltage, enable the fuse again or replace the power
supply unit.