Datasheet
https://www.phoenixcontact.com/us/produkte/2902993
Nov 14, 20132/5
Power supply unit-UNO-PS/1AC/24DC/100W-2902993
Technical data
Input data
Current consumption
1 A (230 V AC)
Inrush surge current
< 40 A (typical)
Power failure bypass
> 20 ms (120 V AC)
Power failure bypass
> 100 ms (230 V AC)
Input fuse
4 A (slow-blow, internal)
Choice of suitable fuses
6 A ... 16 A (Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
24 V DC ±1%
Output current
4.2 A (-25°C ... 55°C)
Derating
55 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Control deviation
< 1 % (change in load, static 10% ... 90%)
Control deviation
< 2 % (Dynamic load change 10% ... 90%, 10 Hz)
Control deviation
< 0.1 % (change in input voltage ±10%)
Residual ripple
< 30 mV
PP
(with nominal values)
Maximum power dissipation NO-Load
< 0.5 W
Power loss nominal load max.
< 11 W
General
Net weight
0.34 kg
Efficiency
> 90 % (for 230 V AC and nominal values)
Insulation voltage input/output
4 kV AC (type test)
Insulation voltage input/output
3 kV AC (routine test)
Protection class
II (in an enclosed control cabinet)
MTBF (IEC 61709, SN 29500)
> 500000 h (According to EN 29500)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Alignable: 0 mm horizontally, 30 mm vertically
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard – Electrical equipment of machines
EN 60204-1
Standard - Electrical safety
IEC 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power
installations and their assembly into electrical power
installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
IEC 60950-1 (SELV) and EN 60204 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard – Protection against electric shock
DIN 57100-410
Standard – Limitation of mains harmonic currents
EN 61000-3-2