Datasheet
https://www.phoenixcontact.com/gb/products/2902061
01/16/2018Page4/10
Loop-powered isolators-MINI MCR-2-UI-I-OLP-2902061
Technical data
Input data
Input resistance of voltage input approx. 100 kΩ (At ≤ 1 V, otherwise approximately 1 MΩ)
Input resistance current input 25 Ω (+ 0.7 V for test diode)
Output data
Number of outputs 1
Current output signal 4 mA ... 20 mA
Max. output current 32 mA
Load/output load current output
< 1000 Ω ((U
B
- 8 V) / 22 mA)
Ripple
< 10 mV
rms
(at 600 Ω)
Power supply
Supply voltage range 8 V DC ... 30 V DC (no separate supply voltage necessary)
Typical current consumption ≤ 20 mA
Power consumption ≤ 600 mW
Connection data
Connection method Screw connection
Single conductor/terminal point, solid, with ferrule, min. 0.2 mm²
Single conductor/terminal point, solid, with ferrule, max. 1.5 mm²
Single conductor/terminal point, solid, without ferrule, min. 0.2 mm²
Single conductor/terminal point, solid, without ferrule, max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Min. AWG conductor cross section, flexible 24
Max. AWG conductor cross section, flexible 12
Stripping length 10 mm
Screw thread M3
General
No. of channels 1
Maximum transmission error ≤ 0.1 % (of final value)
Maximum temperature coefficient 0.01 %/K
Temperature coefficient, typical 0.005 %/K
Limit frequency (3 dB) approx. 30 Hz
Step response (10-90%) 20 ms
Electrical isolation Reinforced insulation in accordance with IEC 61010-1
Overvoltage category II
Degree of pollution 2
Rated insulation voltage 300 V (effective)
Test voltage, input/output/supply 3 kV (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4