Datasheet
https://www.phoenixcontact.com/gb/products/2902061
01/16/2018Page1/10
Loop-powered isolators-MINI MCR-2-UI-I-OLP-2902061
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Output loop-powered 2-way isolator with plug-in connection technology for the electrical isolation of unipolar
and bipolar analog signals. Input configurable via DIP switch. Screw connection technology, standard
configuration.
Product Description
Output loop-powered 2-way isolator with plug-in connection technology for the electrical isolation, conversion, and filtering of analog signals. The
output loop-powered isolator allows operation at an active analog input module. The device is supplied via the current loop of the controller. On
the input side, standard analog signals and non-standard analog signals can be connected, ranging from 2 mA or 50 mV up to 40 mA or 30 V.
These are converted to 4 mA ... 20 mA signals. You can configure the input signals via DIP switches. The measuring transducer supports NFC
communication.
Key Commercial Data
Packing unit 1 STK
GTIN
GTIN 4046356652100
Weight per Piece (excluding packing) 107.900 g
Custom tariff number 85437090
Country of origin Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width 6.2 mm
Height 110.5 mm
Depth 120.5 mm
Ambient conditions
Ambient temperature (operation) -40 °C ... 70 °C