Datasheet
https://www.phoenixcontact.com/pi/products/2902037
04/04/2017Page3/12
Signal conditioner-MINI MCR-2-UI-UI-2902037
Technical data
Output data
Short-circuit current < 32 mA
Load/output load voltage output ≥ 10 kΩ
Load/output load current output ≤ 600 Ω (at 20 mA)
Ripple
< 20 mV
PP
(at 600 Ω)
< 20 mV
PP
(at 600 Ω)
Power supply
Nominal supply voltage 24 V DC
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the
supply voltage. It can be snapped onto a 35 mm DIN rail according to
EN60715))
Typical current consumption 25 mA (Current output, at 24 V DC incl. load)
54 mA (Current output, at 12 V DC incl. load)
Power consumption
≤ 800 mW (at I
OUT
= 20 mA, 9.6 V DC, 600 Ω load)
Connection data
Connection method Screw connection
Single conductor/terminal point, solid, with ferrule, min. 0.2 mm²
Single conductor/terminal point, solid, with ferrule, max. 1.5 mm²
Single conductor/terminal point, solid, without ferrule, min. 0.2 mm²
Single conductor/terminal point, solid, without ferrule, max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Min. AWG conductor cross section, flexible 24
Max. AWG conductor cross section, flexible 12
Stripping length 10 mm
Screw thread M3
General
No. of channels 1
Maximum transmission error ≤ 0.1 % (of final value)
≤ 0.15 % (of final value, at IN: 4 ... 20 mA / OUT: -10 V ... 10 V)
Maximum temperature coefficient 0.01 %/K
Temperature coefficient, typical 0.01 %/K
Limit frequency (3 dB) 30 Hz (via DIP switch)
5 kHz (via DIP switch)
Step response (10-90%) < 8.5 ms (with 30 Hz filter)
Protective circuit Transient protection
Electrical isolation Reinforced insulation in accordance with IEC 61010-1
Overvoltage category II
Degree of pollution 2
Rated insulation voltage 300 V (effective)