Datasheet

https://www.phoenixcontact.com/pi/products/2902015
04/04/2017Page2/11
Repeater power supply-MINI MCR-2-RPSS-I-I-PT-2902015
Technical data
Ambient conditions
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20
Input data
Description of the input Current input (sensor circuit)
Number of inputs 1
Current input signal 4 mA ... 20 mA (repeater power supply and isolator operation)
0 mA ... 20 mA (isolator operation)
Input resistance current input approx. 68 Ω (+ 0.7 V for test diode)
Transmitter supply voltage > 19.5 V
Output data
Output name Current output
Number of outputs 1
Current output signal 4 mA ... 20 mA (repeater power supply and isolator operation)
0 mA ... 20 mA (isolator operation)
Max. output current 24 mA
Load/output load current output ≤ 600 Ω (at 20 mA)
Ripple
< 20 mV
PP
(at 600 Ω)
Transmission Behavior 1:1 to input signal
Power supply
Nominal supply voltage 24 V DC
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the
supply voltage. It can be snapped onto a 35 mm DIN rail according to
EN60715))
Typical current consumption 25 mA (at 24 V DC and in isolator operation)
50 mA (at 24 V DC and in repeater power supply operation)
55 mA (at 12 V DC and in isolator operation)
110 mA (at 12 V DC and in repeater power supply operation)
Power consumption
≤ 1400 mW (at I
OUT
= 20 mA, 9.6 V DC, 600 Ω load)
Connection data
Connection method Push-in connection
Single conductor/terminal point, solid, with ferrule, min. 0.14 mm²
Single conductor/terminal point, solid, with ferrule, max. 2.5 mm²
Single conductor/terminal point, solid, without ferrule, min. 0.14 mm²
Single conductor/terminal point, solid, without ferrule, max. 2.5 mm²
Conductor cross section flexible min. 0.14 mm²
Conductor cross section flexible max. 2.5 mm²
Min. AWG conductor cross section, flexible 24
Max. AWG conductor cross section, flexible 12
Stripping length 10 mm