Datasheet

https://www.phoenixcontact.com/de/products/2902003
04/05/2017Page2/11
Signal conditioner-MINI MCR-2-I4-U-PT-2902003
Technical data
Input data
Number of inputs 1
Configurable/programmable no
Current input signal 4 mA ... 20 mA
Input resistance current input approx. 63 Ω (+ 0.7 V for test diode)
Output data
Number of outputs 1
Configurable/programmable no
Voltage output signal 0 V ... 10 V
Max. output voltage 11 V
Short-circuit current < 15 mA
Load/output load voltage output ≥ 10 kΩ
Ripple
< 20 mV
PP
(at 10 kΩ)
Power supply
Nominal supply voltage 24 V DC
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the
supply voltage. It can be snapped onto a 35 mm DIN rail according to
EN60715))
Typical current consumption 25 mA (24 V DC)
54 mA (12 V DC)
Power consumption ≤ 200 mW (at 9.6 V DC)
Connection data
Connection method Push-in connection
Single conductor/terminal point, solid, with ferrule, min. 0.14 mm²
Single conductor/terminal point, solid, with ferrule, max. 2.5 mm²
Single conductor/terminal point, solid, without ferrule, min. 0.14 mm²
Single conductor/terminal point, solid, without ferrule, max. 2.5 mm²
Conductor cross section flexible min. 0.14 mm²
Conductor cross section flexible max. 2.5 mm²
Min. AWG conductor cross section, flexible 24
Max. AWG conductor cross section, flexible 12
Stripping length 10 mm
General
No. of channels 1
Maximum transmission error 0.1 % (of final value)
Maximum temperature coefficient 0.01 %/K
Temperature coefficient, typical 0.01 %/K
Limit frequency (3 dB) approx. 30 Hz
Step response (10-90%) approx. 10 ms
Protective circuit Transient protection