Data Sheet

https://www.phoenixcontact.com/us/products/2901995
May 3, 20171/9
Loop-powered isolators-MINI MCR-2-I-I-ILP-PT-2901995
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Single-channel input loop-powered 2-way isolator with plug-in connection technology for the electrical
isolation of analog signals. Input signal = output signal: 0(4) mA ... 20 mA. Push-in connection
technology.
Article description
Single-channel input-loop-powered 2-way isolator with plug-in connection technology for the electrical isolation and filtering of analog
signals. The input-loop-powered isolator allows operation with active sensor technology with a supply voltage of 6 V DC to 30 V DC. The
device is powered via the current loop of the sensor. Input signal = output signal: 0(4) mA to 20 mA. The measuring transducer supports
NFC communication. 
Key commercial data
package_quantity
1
GTIN
4046356649261
Technical data
Dimensions
Width
6.2 mm
Height
110.5 mm
Depth
120.5 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Maximum altitude
< 2000 m
Input data
Description of the input
Current input
Configurable/programmable
no
Current input signal
0 mA ... 20 mA
Current input signal
4 mA ... 20 mA
Response current
approx. 200 µA
Input voltage limitation
30 V
Voltage dissipation
3.1 V (I = 20 mA)
Output data

Summary of content (9 pages)