Datasheet

https://www.phoenixcontact.com/us/produkte/2868664
Nov 14, 20133/10
Power supply unit-STEP-PS/ 1AC/24DC/4.2-2868664
Technical data
General
Standard – Electronic equipment for use in electrical power
installations and their assembly into electrical power
installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
IEC 60950-1 (SELV) and EN 60204 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard - Safe isolation
DIN VDE 0106-1010
Standard – Protection against electric shock
DIN 57100-410
Standard – Protection against shock currents, basic
requirements for protective separation in electrical equipment
DIN VDE 0106-101
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Information technology equipment - safety (CB scheme)
CB Scheme
UL approvals
UL/C-UL listed UL 508
UL approvals
UL/C-UL Recognized UL 60950
UL approvals
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
(Hazardous Location)
Surge voltage category
III
Connection data, input
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
12
Stripping length
6.5 mm
Screw thread
M3
Connection data, output
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
12
Stripping length
6.5 mm
Signaling
Output name
LED status indicator
Status display
"DC OK" LED green
Note on status display
U
OUT
> 21.5 V: LED lights up