Datasheet

STEP-PS/1AC/24DC/0.5
104233_en_00 PHOENIX CONTACT 5
Conformance with EMC guideline 2004/108/EC and for low-voltage guideline 2006/95/EC
Noise immunity according to EN 61000-6-2
Electrostatic discharge EN 61000-4-2
Housing Level 3
Contact discharge ± 6 kV (Contact discharge)
Discharge in air ± 8 kV (Air discharge)
Comments Criterion B
Electromagnetic HF field EN 61000-4-3
Housing Level 4
Frequency range 80 MHz ... 3 GHz
Field intensity 10 V/m
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input 4 kV (level 4 - asymmetrical)
Output 2 kV (Level 3 - asymmetrical)
Comments Criterion B
Surge current loads (surge) EN 61000-4-5
Input 4 kV (asymmetrical: Conductor to ground)
2 kV (symmetrical: Conductor to conductor)
Output 2 kV (level 3 - asymmetrical: conductor to ground)
1 kV (Level 3 - symmetrical: Conductor to conductor)
Comments Criterion B
Conducted interference EN 61000-4-6
Input/output Level 3 - asymmetrical
Frequency range 10 kHz ... 80 MHz
Voltage 10 V
Comments Criterion A
Voltage dips EN 61000-4-11
Input (mains buffering > 20 ms)
Comments Criterion A
Emitted interference in acc. with EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) class B used in industry and residential area / EMC 1
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) class B used in industry and residential area / EMC 1