Datasheet

STEP-PS/1AC/12DC/5 Order No.: 2868583
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2868583
PHOENIX CONTACT Deutschland GmbH Page 2 / 7
http://www.phoenixcontact.de May 19, 2010
Technical data
Input data
Nominal input voltage 100 V AC ... 240 V AC
AC input voltage range 85 V AC ... 264 V AC
DC input voltage range 95 V DC ... 250 V DC
AC frequency range 45 Hz ... 65 Hz
DC frequency range 0 Hz
Current consumption Approx. 0.8 A (120 V AC)
Approx. 0.5 A (230 V AC)
Inrush surge current < 15 A (typical)
Power failure bypass > 27 ms (120 V AC)
> 120 ms (230 V AC)
Input fuse 3.15 A (slow-blow, internal)
Name of protection Transient surge protection
Protective circuit/component Varistor
Output data
Nominal output voltage 12 V DC ±1%
Setting range of the output voltage 10 V DC ... 16.5 V DC (> 12 V constant capacity)
Output current 5 A (-25°C ... 55°C)
5.5 A (-25 °C ... 40 °C permanent)
9 A (maximum output current)
Derating From +55°C to 70°C: 2.5% per Kelvin
Connection in parallel Yes, for redundancy and increased capacity
Connection in series Yes
Control deviation < 1 % (change in load, static 10% ... 90%)
< 2 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
Residual ripple < 55 mV
PP
(with nominal values)
Peak switching voltages nominal load < 55 mV
PP
(with nominal values)
Maximum power dissipation idling < 0.5 W
Power loss nominal load max. 8.6 W
General data
Width 72 mm
Height 90 mm