Datasheet

https://www.phoenixcontact.com/us/produkte/2866983
Nov 9, 20132/7
Power supply unit-MINI-SYS-PS-100-240AC/24DC/1.5-2866983
Technical data
Ambient conditions
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, no condensation)
Noise immunity
EN 61000-6-2:2005
Input data
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range AC
85 V AC ... 264 V AC
AC frequency range
45 Hz ... 65 Hz
Current consumption
0.75 A (120 V AC)
Current consumption
0.45 A (230 V AC)
Inrush surge current
< 15 A (0.6 A
2
s)
Power failure bypass
> 35 ms (120 V AC)
Power failure bypass
> 150 ms (230 V AC)
Input fuse
3.15 A (slow-blow, internal)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
24 V DC ±1%
Output current
1.5 A (-25 °C ... 60 °C)
Output current
2 A (with POWER BOOST, -25°C ... 40°C permanent)
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity.Maximum of 2
devices for redundancy on DIN rail connector.
Connection in series
No
Max. capacitive load
Unlimited
Control deviation
< 1 % (change in load, static 10% ... 90%)
Control deviation
< 3 % (change in load, dynamic 10% ... 90%)
Control deviation
< 0.1 % (change in input voltage ±10%)
Residual ripple
< 40 mV
PP
(20 MHz)
Peak switching voltages idling
< 20 mV
PP
(20 MHz)
Peak switching voltages nominal load
< 20 mV
PP
(20 MHz)
Maximum power dissipation NO-Load
1.5 W
Power loss nominal load max.
6.5 W
General
Net weight
0.25 kg
Operating voltage display
Green LED
Efficiency
> 84 % (for 230 V AC and nominal values)
Insulation voltage input/output
4 kV (type test)
Insulation voltage input/output
3 kV (Routine test)
Protection class
II (in an enclosed control cabinet)
MTBF (IEC 61709, SN 29500)
> 2789000 h (According to EN 29500)