Datasheet
PHOENIX CONTACT page 5 of 8
Power Supply Unit, Primary Switched, Narrow Design – MINI-SYS-PS-100-240AC/24DC/1.5
6. Installation
24V 13 14
71 72
63 64
24V 0V 0V
MINI-SYS-POWER
DC
OK
IN AC 100-240 V
24V 0V 0V
L
N
NC
24V 13 14
OUT DC 24V 1.5A
MINI-SYS-PS-100-240AC/24DC/1.5
Order No.: 28 66 98 3
U
INDUSTRIAL
CONTROL
EQUIPMENT
1YD8
LISTED
APPROVALS
u
INFORMATION
TECHNOLOGY
EQUIPMENT
Power Supply
INPUT
OUTPUT
AC:
100-240V
50-60Hz
Range:
85-264V
0.4-0.2A
DC:
90-350V
0.4-0.2A
24V DC
±1%
1.5A
Read installation instructions
before connecting to mains
www.interface.phoenixcontact.com
TEMPERATURE
- 25 … + 60 °C
- 13 … + 140 °F
–
2
5
Figure 05
Mounting Removal
Figure 07
6.1. Mounting
The power supply unit can be snapped onto all
DIN rails according to EN 60715. The device must be
mounted horizontally (input terminal blocks facing
downwards).
Installation Dimensions
To ensure sufficient convection, a
minimum spacing of 5 cm (1.969 in.) to
other modules is required above
and below the device.
MINI-SYS-POWER
IN AC 100-240 V
24V 0V 0V
L
N
NC
24V 13 14
OUT DC 24V 1.5A
DC
OK
50 mm
(1.969 in.)
99 mm (3.898 in.)
50 mm
(1.969 in.)
35 mm
(1.378 in.)
Installation depth: 106 mm [4.173 in.] (+ DIN rail)
Figure 06
102.5 mm (4.035 in.)
95 mm (3.740 in.)
199 mm (7.835 in.)
Mounting:
Place the module with the DIN rail guideway on the
top edge
of the DIN rail and then snap it
downwards
.
The DIN rail bus connector is snapped onto the DIN
rail. The housing is mounted on the DIN rail by
swiveling it into place.
Removal:
Release the snap-on catch using a screwdriver and
then detach the module from the
bottom edge
of the
DIN rail.