Datasheet

PHOENIX CONTACT page 2 of 8
Solid Stranded Torque
[mm
2
]AWG [Nm] [Ib in]
Input 0.2 - 2.5 0.2 - 2.5 25 - 14 0.5 - 0.6 4.4 - 5.3
Output 0.2 - 2.5 0.2 - 2.5 25 - 14 0.5 - 0.6 4.4 - 5.3
Signal 0.2 - 2.5 0.2 - 2.5 25 - 14 0.5 - 0.6 4.4 - 5.3
Description
Power supply unit
,
primary switched, narrow design
Technical Data
Input Data
1
Nominal input voltage
Input voltage range (current consumption)
Frequency
Current consumption (for nominal values)
Inrush current limiting/I
2
t (+25°C [+77°F])
Mains buffering for a nominal load (typical)
Switch-on time after applying the mains voltage
Transient surge protection
Input fuse, internal
Recommended fuse
Output Data
2
Nominal output voltage U
N
/tolerance
Output current during convection cooling and
nominal values POWER BOOST I
BOOST
-25 - 40°C (-13 - 104°F)
Nominal output current I
N
-25°C to +60°C (-13°F to +140°F)
Derating
Short-circuit current limit
Startup of capacitive loads
System deviation on: Static load change 10 - 90%
Dynamic load change 10 - 90%
Input voltage change ±10%
Maximum power dissipation No load/nominal load
Level of efciency (typical)
Response time U
OUT
(10% - 90%)
Residual ripple/switching peaks (20 MHz)
Can be connected in parallel
Internal surge protection
Resistance to return supply
Signal Output Data
DC OK (electrically isolated) U
out
> 21.5 V DC
=
contact closed
LED (U
out
> 21.5 V DC
=
LED permanently on)
MINI-SYS-PS-100-240AC/24DC/1.5
1 AC
U u
Type Order No.
Pcs.
Pkt.
MINI-SYS-PS-100-240AC/24DC/1.5 28 66 98 3
1
100 - 240 V AC (wide-range voltage input)
85 - 264 V AC
45 - 65 Hz
0.75 A (120 V AC)/ 0.45 A (230 V AC), approximately
< 15 A/< 0.6 A
2
s, typical
> 20 ms (120 V AC)/> 110 ms (230 V AC)
< 0.5 s
Varistor
T3.15 AL250V (3.15 A) (device protection)
6 A, 10 A circuit breakers, characteristic B (EN 60 898)
24 V DC/±1%
2 A (U
OUT
= 24 V)
1.5 A (U
OUT
= 24 V)
From +60°C (+140°F), 2.5% per Kelvin
7 A
Unlimited
< 1%, typical
< 3%, typical
< 0.1%, typical
2.5 W/12 W
> 84% (at 230 V AC and at nominal values)
< 2 ms, typical
< 100 mV
pp
(for nominal values)
To increase redundancy and power
Ye s, limited to 30 V DC, approximately
30 V DC
30 V AC/DC, maximum; 1 A, maximum
Green LED
99 mm
(3.898 in.)
35 mm
(
1.378 in.
)
102.5 mm
(4.035 in.)
L
N
NC
13
24V
24V
14
0V
0V
Power Supply Unit, Primary Switched, Narrow Design – MINI-SYS-PS-100-240AC/24DC/1.5
3. Technical Data
7 mm (0.28 in.)