General data
Width 96 mm
Height 130 mm
Depth 176 mm
Width with alternative assembly 177.5 mm
Height with alternative assembly 130 mm
99 mm
Net weight 2.5 kg
Operating voltage display Green LED
Efficiency > 94 % (at 400 V AC and nominal values)
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Degree of protection IP20
Protection class I
MTBF (IEC 61709, SN 29500) > 500000 h (According to IEC 61709)
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, no condensation)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions Can be aligned: 5 mm horizontally, 15 mm next to active
components, 5 cm vertically
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Noise immunity EN 61000-6-2:2005
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard – Electrical equipment of machines EN 60204
Standard - Safety of transformers IEC 61558-2-17
Standard - Electrical safety IEC 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in
electrical power installations and their assembly
into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0100-410
DIN VDE 0106-101
Standard – Protection against electric shock DIN 57100-410
Standard – Protection against shock currents,
basic requirements for protective separation in
electrical equipment
DIN VDE 0106-101