Datasheet
https://www.phoenixcontact.com/us/produkte/2866792
Nov 14, 20133/10
Power supply unit-QUINT-PS/ 3AC/24DC/20-2866792
Technical data
General
Operating voltage display
Green LED
Efficiency
> 93 % (at 400 V AC and nominal values)
Insulation voltage input/output
4 kV AC (type test)
Insulation voltage input/output
2 kV AC (routine test)
Protection class
I
MTBF (IEC 61709, SN 29500)
> 534000 h
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Alignable: 5 mm horizontally, 15 mm next to active components,
50 mm vertically
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard – Electrical equipment of machines
EN 60204
Standard - Electrical safety
IEC 60950-1/VDE 0805 (SELV)
Shipbuilding approval
Germanischer Lloyd (EMC 1), ABS, LR, RINA, NK, DNV, BV
Standard – Electronic equipment for use in electrical power
installations and their assembly into electrical power
installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
IEC 60950-1 (SELV) and EN 60204 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard - Safe isolation
DIN VDE 0106-1010
Standard – Protection against electric shock
DIN 57100-410
Standard – Protection against shock currents, basic
requirements for protective separation in electrical equipment
DIN VDE 0106-101
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Standard - Equipment safety
GS (tested safety)
Approval - requirement of the semiconductor industry with
regard to mains voltage dips
SEMI F47-0706 Compliance Certificate
Information technology equipment - safety (CB scheme)
CB Scheme
UL approvals
UL Listed UL 508
UL approvals
UL/C-UL Recognized UL 60950 (3-wire + PE, star net)
UL approvals
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
(Hazardous Location)
Surge voltage category
III
Connection data, input
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
6 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
4 mm²
Conductor cross section AWG/kcmil min.
18
Conductor cross section AWG/kcmil max
10
Stripping length
7 mm
Screw thread
M4