Datasheet

https://www.phoenixcontact.com/us/produkte/2866792
Nov 14, 20132/10
Power supply unit-QUINT-PS/ 3AC/24DC/20-2866792
Technical data
Input data
Nominal input voltage range
3x 400 V AC ... 500 V AC
Input voltage range AC
3x 320 V AC ... 575 V AC
Input voltage range AC
2x 360 V AC ... 575 V AC (Not approved by UL)
Input voltage range DC
450 V DC ... 800 V DC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Current consumption
3x 1.6 A (400 V AC)
Current consumption
3x 1.3 A (500 V AC)
Current consumption
approx. 2x 3.2 A (400 V AC)
Current consumption
approx. 2x 2.8 A (500 V AC)
Inrush surge current
< 20 A (typical)
Power failure bypass
> 20 ms (400 V AC)
Power failure bypass
> 30 ms (500 V AC)
Choice of suitable fuses
6 A ... 16 A (Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor, gas-filled surge arrester
Output data
Nominal output voltage
24 V DC ±1%
Setting range of the output voltage
18 V DC ... 29.5 V DC (> 24 V constant capacity)
Output current
20 A (-25°C ... 60°C, U
OUT
= 24 V DC)
Output current
26 A (with POWER BOOST, -25°C ... 40°C permanently, U
OUT
= 24
V DC)
Output current
120 A (SFB technology, 12 ms)
Magnetic fuse tripping
B2
Magnetic fuse tripping
B4
Magnetic fuse tripping
B6
Magnetic fuse tripping
B10
Magnetic fuse tripping
B16
Magnetic fuse tripping
C2
Magnetic fuse tripping
C4
Magnetic fuse tripping
C6
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Residual ripple
< 40 mV
PP
(with nominal values)
Peak switching voltages nominal load
< 40 mV
PP
(at nominal values, 20 MHz)
Maximum power dissipation NO-Load
11 W
Power loss nominal load max.
40 W
General
Net weight
1.5 kg