Datasheet
QUINT-PS/3AC/24DC/20
103132_en_00 PHOENIX CONTACT 5
Protection against electric shock, basic requirements for safe isolation in
electrical equipment
DIN VDE 0106-101
Limitation of mains harmonic currents EN 61000-3-2
Device safety GS (tested safety)
Network variants (undervoltage) Semi F47-200
Certificate CB Scheme
Approvals
UL rating UL Listed UL 508
UL/C-UL Recognized UL 60950 (3-wire + PE, star net)
Conformance with EMC directive 2004/108/EC
Noise immunity according to EN 61000-6-2
Electrostatic discharge EN 61000-4-2
Housing Level 4
Contact discharge 8 kV (Contact discharge)
Discharge in air 15 kV (Air discharge)
Comments Criterion B
Electromagnetic HF field EN 61000-4-3
Housing Level 4
Frequency range 80 MHz ... 1000 MHz
1.4 GHz ... 2 GHz
Field intensity 20 V/m
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input 4 kV (level 4 - asymmetrical: conductor to ground)
Output 2 kV (Level 3 - asymmetrical)
Signal 1 kV (level 2 - asymmetrical: conductor to ground)
Comments Criterion B
Surge current loads (surge) EN 61000-4-5
Input 6 kV (asymmetrical: Conductor to ground)
3 kV (symmetrical: Conductor to conductor)
Output 2 kV (level 3 - asymmetrical: conductor to ground)
Signal 1 kV (level 1 - symmetrical: conductor to conductor)
Comments Criterion B
Conducted interference EN 61000-4-6
Input/Output/Signal Level 3 - asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V
Comments Criterion A
Voltage dips EN 61000-4-11
Input (Mains buffering time > 20 ms (Semi F47-200))
Comments Criterion B
Emitted interference in acc. with EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Standards