Power supply unit-QUINT-PS/ 1AC/24DC/40-2866789
Technical data
Ambient conditions
Noise immunity
EN 61000-6-2:2005
Input data
Nominal input voltage range
100 V AC ... 240 V AC
Nominal input voltage range
120 V DC ... 300 V DC (UL 508: ≤ 250 V DC)
Input voltage range AC
85 V AC ... 264 V AC
Input voltage range DC
90 V DC ... 300 V DC (UL 508: ≤ 250 V DC)
Short-term input voltage
max. 300 V AC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Current consumption
8.8 A (120 V AC)
Current consumption
4.6 A (230 V AC)
Current consumption
8.8 A (120 V DC)
Current consumption
4.2 A (250 V DC)
Inrush surge current
< 15 A (typical)
Power failure bypass
> 20 ms (120 V AC)
Power failure bypass
> 20 ms (230 V AC)
Input fuse
20 A (fast blow, internal)
Choice of suitable fuses
16 A ... 20 A (Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
24 V DC ±1%
Setting range of the output voltage
18 V DC ... 29.5 V DC (> 24 V constant capacity)
Output current
40 A (-25°C ... 60°C, U
OUT
= 24 V DC)
Output current
45 A (with POWER BOOST, -25°C ... 40°C permanently, U
OUT
= 24
V DC)
Output current
215 A (SFB technology, 12 ms)
Output current
215 A (U
In
≥ 100 V AC, ≥ 120 V DC)
Magnetic fuse tripping
B2
Magnetic fuse tripping
B4
Magnetic fuse tripping
B6
Magnetic fuse tripping
B10
Magnetic fuse tripping
B16
Magnetic fuse tripping
B25
Magnetic fuse tripping
C2
Magnetic fuse tripping
C4
Magnetic fuse tripping
C6
Magnetic fuse tripping
C13
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased power (see data sheet Section
15/Parallel operation function)