Datasheet

https://www.phoenixcontact.com/us/produkte/2866789
11.04.2013Page3/13
Power supply unit-QUINT-PS/ 1AC/24DC/40-2866789
Technical data
Output data
Connection in parallel
Yes, for redundancy and increased power (see data sheet Section 15/
Parallel operation function)
Connection in series Yes
Residual ripple
< 30 mV
PP
(with nominal values)
Maximum power dissipation NO-Load 14 W
Power loss nominal load max. 80 W
General data
Width 180 mm
Height 130 mm
Depth 125 mm
Width with alternative assembly 122 mm
Height with alternative assembly 130 mm
Depth with alternative assembly 183 mm
Net weight 3.3 kg
Efficiency > 92 % (for 230 V AC and nominal values)
Insulation voltage input/output 4 kV AC (type test)
Insulation voltage input/output 2 kV AC (routine test)
Degree of protection IP20
Protection class I
MTBF (IEC 61709, SN 29500) > 530000 h
Ambient temperature (operation) -25 °C ... 70 °C (> 60°C derating, startup at -40°C type-tested)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, no condensation)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions
Alignable: 5 mm horizontally, 15 mm next to active components, 50 mm
vertically
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Noise emission EN 50081-2
Noise immunity EN 61000-6-2:2005
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard – Electrical equipment of machines EN 60204
Standard - Electrical safety IEC 60950-1/VDE 0805 (SELV)
Shipbuilding approval Germanischer Lloyd (EMC 2), ABS, LR, RINA, NK, DNV, BV
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard - Safe isolation DIN VDE 0106-101