Datasheet

https://www.phoenixcontact.com/us/produkte/2866763
Nov 14, 20132/13
Power supply unit-QUINT-PS/ 1AC/24DC/10-2866763
Technical data
Ambient conditions
Noise immunity
EN 61000-6-2:2005
Input data
Nominal input voltage range
100 V AC ... 240 V AC
Nominal input voltage range
110 V DC ... 250 V DC
Input voltage range AC
85 V AC ... 264 V AC
Input voltage range DC
90 V DC ... 350 V DC (UL 508: ≤ 300 V DC)
Short-term input voltage
300 V AC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Current consumption
2.24 A (120 V AC)
Current consumption
1.33 A (230 V AC)
Current consumption
2.45 A (110 V DC)
Current consumption
1.05 A (250 V DC)
Inrush surge current
< 15 A (typical)
Power failure bypass
> 32 ms (120 V AC)
Power failure bypass
> 36 ms (230 V AC)
Input fuse
10 A (slow-blow, internal)
Choice of suitable fuses
10 A ... 16 A (Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
24 V DC ±1%
Setting range of the output voltage
18 V DC ... 29.5 V DC (> 24 V constant capacity)
Output current
10 A (-25°C ... 60°C, U
OUT
= 24 V DC)
Output current
15 A (with POWER BOOST, -25°C ... 40°C permanently, U
OUT
= 24
V DC)
Output current
60 A (SFB technology, 12 ms)
Output current
15 A (U
In
≥ 100 V AC, ≥ 110 V DC)
Magnetic fuse tripping
B2
Magnetic fuse tripping
B4
Magnetic fuse tripping
B6
Magnetic fuse tripping
C2
Magnetic fuse tripping
C4
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Control deviation
< 1 % (change in load, static 10% ... 90%)
Control deviation
< 2 % (change in load, dynamic 10% ... 90%)
Control deviation
< 0.1 % (change in input voltage ±10%)
Residual ripple
< 50 mV
PP
(with nominal values)
Maximum power dissipation NO-Load
9.1 W