Datasheet

https://www.phoenixcontact.com/us/produkte/2866718
Nov 14, 20132/9
Power supply unit-QUINT-PS/ 1AC/12DC/15-2866718
Technical data
Input data
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range AC
85 V AC ... 264 V AC
Input voltage range DC
90 V DC ... 350 V DC (UL 508: ≤ 250 V DC)
Short-term input voltage
300 V AC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Current consumption
1.9 A (120 V AC)
Current consumption
0.9 A (230 V AC)
Inrush surge current
< 15 A (typical)
Power failure bypass
> 65 ms (120 V AC)
Power failure bypass
> 65 ms (230 V AC)
Input fuse
6.3 A (slow-blow, internal)
Choice of suitable fuses
10 A ... 16 A (Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
12 V DC ±1%
Setting range of the output voltage
5 V DC ... 18 V DC (> 12 V constant capacity)
Output current
15 A (-25 °C ... 60 °C)
Output current
16 A (with POWER BOOST, -25°C ... 40°C permanent)
Output current
60 A (SFB technology, 12 ms)
Output current
60 A (U
In
≥ 100 V AC)
Magnetic fuse tripping
B2
Magnetic fuse tripping
B4
Magnetic fuse tripping
B6
Magnetic fuse tripping
C2
Magnetic fuse tripping
C4
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Control deviation
< 1 % (change in load, static 10% ... 90%)
Control deviation
< 2 % (change in load, dynamic 10% ... 90%)
Control deviation
< 0.1 % (change in input voltage ±10%)
Residual ripple
< 10 mV
PP
(with nominal values)
Maximum power dissipation NO-Load
5 W
Power loss nominal load max.
21 W
General
Net weight
1.1 kg
Efficiency
> 89 % (for 230 V AC and nominal values)
Insulation voltage input/output
4 kV AC (type test)