Datasheet
https://www.phoenixcontact.com/us/produkte/2866705
Nov 13, 20132/11
Power supply unit-QUINT-PS/ 3AC/24DC/10-2866705
Technical data
Input data
Nominal input voltage range
3x 400 V AC ... 500 V AC
Input voltage range AC
3x 320 V AC ... 575 V AC
Input voltage range AC
2x 360 V AC ... 575 V AC
Input voltage range DC
450 V DC ... 800 V DC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Current consumption
3x 1.2 A (400 V AC)
Current consumption
3x 1 A (500 V AC)
Inrush surge current
< 15 A (typical)
Power failure bypass
> 20 ms (400 V AC)
Power failure bypass
> 30 ms (500 V AC)
Choice of suitable fuses
6 A ... 16 A (Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor, gas-filled surge arrester
Output data
Nominal output voltage
24 V DC ±1%
Setting range of the output voltage
18 V DC ... 29.5 V DC (> 24 V constant capacity)
Output current
10 A (-25°C ... 60°C, U
OUT
= 24 V DC)
Output current
15 A (with POWER BOOST, -25°C ... 40°C permanently, U
OUT
= 24
V DC)
Output current
60 A (12 ms)
Magnetic fuse tripping
B2
Magnetic fuse tripping
B4
Magnetic fuse tripping
B6
Magnetic fuse tripping
C2
Magnetic fuse tripping
C4
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Residual ripple
< 20 mV
PP
(with nominal values)
Peak switching voltages nominal load
< 20 mV
PP
(at nominal values, 20 MHz)
Maximum power dissipation NO-Load
7 W
Power loss nominal load max.
19 W
General
Net weight
1.1 kg
Operating voltage display
Green LED
Efficiency
> 93 % (at 400 V AC and nominal values)
Insulation voltage input/output
4 kV AC (type test)
Insulation voltage input/output
2 kV AC (routine test)
Protection class
I