Datasheet
https://www.phoenixcontact.com/gb/products/2866695
01/16/2018Page5/9
Power supply unit-QUINT-PS/1AC/48DC/20-2866695
Technical data
Standards and Regulations
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard – Protection against shock currents, basic requirements for
protective separation in electrical equipment
EN 50178
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard - Equipment safety BG (design tested)
Shipbuilding approval DNVGL(EMCA)
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
(Hazardous Location)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Information technology equipment - safety (CBscheme)
IEC 60950 (2
nd
Edition)
Rail applications EN 50121-4
Overvoltage category (EN 62477-1) III
Assembly instructions
alignable: P
N
≥50 %, 5 mm horizontally, 15 mm next to active
components, 50 mm vertically
alignable: P
N
<50 %, 0 mm horizontally, 40 mm vertikaly top, 20 mm
vertikaly bottom
Environmental Product Compliance
China RoHS Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Block diagram
13
I < I
N
DC OK
14
L (+)
N (-)
active
PFC
Classifications
eCl@ss
eCl@ss 4.0 27040702
eCl@ss 4.1 27040702