Limitation of mains harmonic currents EN 61000-3-2
Device safety GS (tested safety)
Network variants (undervoltage) Semi F47-200
Certificate CB Scheme
Approvals
UL approvals UL applied for
Conformance with EMC guideline 2004/108/EC and for low-voltage guideline 2006/95/EC
Noise immunity according to EN 61000-6-2
Electrostatic discharge EN 61000-4-2
Housing Level 4
Contact discharge 8 kV
Discharge in air 15 kV
Comments Criterion B
Electromagnetic HF field EN 61000-4-3
Housing Level 4
Frequency range 80 MHz ... 1000 MHz
Field intensity 20 V/m
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input 4 kV (level 4 - asymmetrical)
Output 2 kV (level 1 - asymmetrical)
Signal 1 kV (level 1 - asymmetrical)
Comments Criterion B
Surge current loads (surge) EN 61000-4-5
Input 4 kV (inst. class 4 - asymmetrical: conductor to ground)
2 kV (inst. class 4 -symmetrical: conductor to conductor)
Output 2 kV (level 3 - asymmetrical: conductor to ground)
1 kV (level 1 - symmetrical: conductor to conductor)
Signal 1 kV (level 3 - asymmetrical: conductor to ground)
Comments Criterion B
Conducted interference EN 61000-4-6
Input/Output/Signal Level 3 - asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V
Comments Criterion A
Voltage dips EN 61000-4-11
Input (mains buffering > 20 ms)
Comments Criterion B
Emitted interference in acc. with EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential