Datasheet
https://www.phoenixcontact.com/ch/products/2866679
11/24/2016Page2/8
Power supply unit-QUINT-PS/1AC/48DC/ 5-2866679
Technical data
Dimensions
Depth with alternative assembly 63 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 95 % (at 25 °C, non-condensing)
Noise immunity EN 61000-6-2:2005
Maximum altitude 5000 m
Input data
Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 85 V AC ... 264 V AC
90 V DC ... 350 V DC
Dielectric strength maximum 300 V AC
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Discharge current to PE < 3.5 mA
Current consumption 2.8 A (120 V AC)
1.2 A (230 V AC)
2.4 A (110 V DC)
1.2 A (220 VDC)
Inrush surge current < 15 A (typical)
Power failure bypass > 40 ms (120 V AC)
> 40 ms (230 V AC)
Input fuse 6.3 A (slow-blow, internal)
Choice of suitable circuit breakers 10 A ... 16 A (AC: Characteristics B, C, D, K)
Type of protection Transient surge protection
Protective circuit/component Varistor
Output data
Nominal output voltage 48 V DC ±1%
Setting range of the output voltage (U
Set
)
30 V DC ... 56 V DC (> 48VDC, constant capacity restricted)
Nominal output current (I
N
) 5 A (-25°C ... 60°C, U
OUT
= 48 V DC)
POWER BOOST (I
Boost
) 7.5 A (-25°C...40°C permanent, U
OUT
= 48VDC )
Selective Fuse Breaking (I
SFB
)
30 A (12 ms)
Derating 60 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series No
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)