Datasheet

https://www.phoenixcontact.com/us/produkte/2866653
Nov 9, 20132/6
Power supply unit-MINI-PS-100-240AC/24DC/1.5/EX-2866653
Technical data
Ambient conditions
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
100 % (condensation permitted)
Input data
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range AC
85 V AC ... 264 V AC
AC frequency range
45 Hz ... 65 Hz
Current consumption
0.75 A (120 V AC)
Current consumption
0.45 A (230 V AC)
Inrush surge current
< 15 A (typical)
Power failure bypass
> 20 ms (120 V AC)
Power failure bypass
> 100 ms (230 V AC)
Input fuse
3.15 A (slow-blow, internal)
Output data
Nominal output voltage
24 V DC ±1%
Output current
1.5 A (-25 °C ... 60 °C)
Output current
2 A (with POWER BOOST, -25 °C ... 40 °C)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Residual ripple
< 40 mV
PP
(with nominal values)
Peak switching voltages nominal load
< 20 mV
PP
(20 MHz)
Maximum power dissipation NO-Load
2.5 W
Power loss nominal load max.
12 W
General
Net weight
0.25 kg
Efficiency
> 84 % (for 230 V AC and nominal values)
Insulation voltage input/output
4 kV AC (type test)
Insulation voltage input/output
3 kV AC (routine test)
Protection class
II (in an enclosed control cabinet)
MTBF (IEC 61709, SN 29500)
> 2789000 h (According to EN 29500)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Can be aligned: Horizontally 0 mm, vertically 50 mm
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Declaration of conformity in acc. with EN 60079-15
 II 3 G Ex nAC IIC T4 X
ATEX
 II 3 G Ex nAC IIC T4
Standard – Electrical equipment of machines
EN 60204
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power
installations and their assembly into electrical power
installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
EN 60950-1 (SELV) and EN 60204 (PELV)
Standard - Safe isolation
DIN VDE 0100-410