Datasheet

https://www.phoenixcontact.com/us/produkte/2866514
Nov 9, 20132/5
Redundancy module-TRIO-
DIODE/12-24DC/2X10/1X20-2866514
Technical data
Input data
Nominal input voltage range
10 V DC ... 30 V DC
Input voltage range DC
[NO ASSET AVAILABLE: TXB,6776478,P]
Nominal input current I
N
2x 10 A (-25°C ... 55°C)
Nominal input current I
N
1x 20 A (-25°C ... 55°C)
Maximum current I
max
2x 15 A (-25°C ... 40°C)
Maximum current I
max
1x 30 A (-25°C ... 40°C)
Output data
Output current
20 A (Increasing power)
Output current
10 A (Redundancy)
Derating
55 °C ... 70 °C (2.5%/K)
Power loss nominal load max.
7 W (I
OUT
= 10 A)
General
Net weight
0.37 kg
Efficiency
> 97 %
Protection class
III
MTBF (IEC 61709, SN 29500)
> 10000000 h (According to EN 29500)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Can be aligned: Horizontally 0 mm, vertically 50 mm
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Low Voltage Directive
Conformance with Low Voltage Directive 2006/95/EC
Standard – Electrical equipment of machines
EN 60204
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power
installations and their assembly into electrical power
installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
IEC 60950-1 (SELV) and EN 60204 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard - Safe isolation
DIN VDE 0106-1010
Standard – Protection against electric shock
DIN 57100-410
Standard – Protection against shock currents, basic
requirements for protective separation in electrical equipment
DIN VDE 0106-101
UL approvals
UL/C-UL listed UL 508
UL approvals
UL/C-UL Recognized UL 60950
Connection data, input
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²