Power supply unit-TRIO-PS/ 1AC/12DC/10-2866488
Technical data
Input data
Current consumption
0.9 A (230 V AC)
Nominal power consumption
(> 12 V constant capacity)
Inrush surge current
< 15 A
Power failure bypass
> 20 ms (120 V AC)
Power failure bypass
> 86 ms (230 V AC)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
12 V DC ±1%
Setting range of the output voltage
10 V DC ... 18 V DC (> 12 V constant capacity)
Output current
10 A (-25°C ... 55°C)
Derating
55 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Max. capacitive load
Unlimited
Current limitation
Approx. 12 A (in the event of a short-circuit)
Control deviation
< 1 % (change in load, static 10% ... 90%)
Control deviation
< 2 % (change in load, dynamic 10% ... 90%)
Control deviation
< 0.1 % (change in input voltage ±10%)
Residual ripple
< 20 mV
PP
Peak switching voltages nominal load
< 70 mV
PP
Maximum power dissipation NO-Load
1.1 W
Power loss nominal load max.
18 W
General
Net weight
0.6 kg
Operating voltage display
Green LED
Efficiency
> 86 % (for 230 V AC and nominal values)
Insulation voltage input/output
4 kV AC (type test)
Insulation voltage input/output
2 kV AC (routine test)
Protection class
I, with PE connection
MTBF (IEC 61709, SN 29500)
> 1871000 h (According to EN 29500)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Can be aligned: Horizontally 0 mm, vertically 50 mm
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard – Electrical equipment of machines
EN 60204
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard - Electrical safety
EN 61558-2-17
Standard – Electronic equipment for use in electrical power
installations and their assembly into electrical power
installations
EN 50178/VDE 0160 (PELV)