Datasheet
https://www.phoenixcontact.com/us/produkte/2865586
Nov 14, 20134/8
Temperature measuring transducer-MACX MCR-EX-SL-TC-I-
NC-2865586
Technical data
Safety characteristic data
λ
DU
3.24 x 10
-8
(32.4 FIT)
λ
DD
3.14 x 10
-7
(314 FIT)
Probability of a hazardous failure on demand (PFD
AVG
)
1.31 x 10
-4
(1 year)
Probability of a hazardous failure on demand (PFD
AVG
)
2.62 x 10
-4
(2 years)
Probability of a hazardous failure on demand (PFD
AVG
)
3.93 x 10
-4
(3 years)
Probability of a hazardous failure on demand (PFD
AVG
)
6.55 x 10
-4
(5 years)
Probability of a hazardous failure on demand (PFD
AVG
)
9.17 x 10
-4
(7 years)
Probability of a hazardous failure on demand (PFD
AVG
)
1.05 x 10
-3
(8 years)
Diagnostic coverage (DC)
90.7 %
Integrity requirement
IEC 61508 - High demand
Architecture
Single-channel, 1oo1
Equipment type
Type B
Safety Integrity Level (SIL)
Up to 2
Safe Failure Fraction (SFF)
90.7 %
MTBF
123 Years
λ
SU
1.42 x 10
-7
(150 FIT)
λ
SD
4.38 x 10
-7
(438 FIT)
λ
DU
3.24 x 10
-8
(32.4 FIT)
λ
DD
3.14 x 10
-7
(314 FIT)
Probability of a hazardous failure per hour (PFH
D
)
3,24 x 10
-8
Diagnostic coverage (DC)
90.7 %
Safety data
Max. output voltage U
o
6 V
Max. output current I
o
4.7 mA
Max. output power P
o
7 mW
Gas group
IIC
Max. external inductivity L
o
100 mH
Max. external capacity C
o
1.5 µF
Gas group
IIC
Max. external inductivity L
o
10 mH
Max. external capacity C
o
1.9 µF
Gas group
IIC
Max. external inductivity L
o
1 mH
Max. external capacity C
o
2.7 µF
Gas group
IIB
Max. external inductivity L
o
100 mH
Max. external capacity C
o
7 µF