Datasheet

https://www.phoenixcontact.com/us/produkte/2865405
Nov 14, 20133/7
Output signal conditioner-MACX MCR-EX-SL-IDSI-I-2865405
Technical data
General
Electrical isolation
300 V
rms
(Rated insulation voltage (surge voltage category II;
pollution degree 2, safe isolation as per EN 61010-1))
Name
Output/input
Electrical isolation
375 V (Peak value in accordance with EN 60079-11)
Name
Output/supply
Electrical isolation
375 V (Peak value in accordance with EN 60079-11)
Conformance
CE-compliant, additionally EN 61326
ATEX
 II (1) G [Ex ia Ga] IIC
ATEX
 II (1) D [Ex ia Da] IIIC
ATEX
 II 3(1) G Ex nA [ia Ga] IIC T4 Gc
IECEx
[Ex ia Ga] IIC
IECEx
[Ex ia Da] IIIC
IECEx
Ex nA [ia Ga] IIC T4 Gc
UL, USA / Canada
Class I Div 2; IS for Class I, II, III Div 1
Functional safety (SIL)
SIL 2 according to EN 61508
Data communication (bypass)
HART function
Yes
Protocols supported
HART
Safety characteristic data
Integrity requirement
IEC 61508 - Low demand
Equipment type
Type A
Safety Integrity Level (SIL)
Up to 2
Safe Failure Fraction (SFF)
94.68 %
λ
SU
4.965 x 10
-7
(496.5 FIT)
λ
SD
0
λ
DU
2.79 x 10
-8
(27.9 FIT)
λ
DD
0
Probability of a hazardous failure on demand (PFD
AVG
)
1.22 x 10
-4
(1 year)
Probability of a hazardous failure on demand (PFD
AVG
)
6.1 x 10
-4
(5 years)
Probability of a hazardous failure on demand (PFD
AVG
)
12.2 x 10
-4
(10 years)
Diagnostic coverage (DC)
(DC
S
= 0%, DC
D
= 0%)
Integrity requirement
IEC 61508 - High demand
Equipment type
Type A
Safety Integrity Level (SIL)
Up to 2
Safe Failure Fraction (SFF)
94.68 %
λ
SU
4.965 x 10
-7
(496.5 FIT)
λ
SD
0
λ
DU
2.79 x 10
-8
(27.9 FIT)
λ
DD
0