Datasheet
https://www.phoenixcontact.com/us/produkte/2865405
Nov 14, 20132/7
Output signal conditioner-MACX MCR-EX-SL-IDSI-I-2865405
Technical data
Input data
Current input signal
4 mA ... 20 mA
Input voltage limitation
5.4 V (at 20 mA)
Input impedance
> 100 kΩ (If there is a line fault)
Output data
Signal output
Current output
Current output signal
0 mA ... 20 mA
Current output signal
4 mA ... 20 mA
Transmission Behavior
1:1 to input signal
Load/output load current output
< 800 Ω (at 20 mA)
Output ripple
< 20 mV
rms
Power supply
Supply voltage range
19.2 V DC ... 30 V DC
Max. current consumption
< 46 mA (at 24 V DC / 20 mA)
Power consumption
< 1.1 W (at 24 V DC / 20 mA)
Connection data
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
14
Stripping length
7 mm
Screw thread
M3
Connection method
Screw connection
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
General
No. of channels
1
Maximum transmission error
< 0.1 % (of final value)
Maximum temperature coefficient
< 0.01 %/K
Step response (10-90%)
< 140 µs
Status display
Green LED (supply voltage)
Inflammability class according to UL 94
V0
Pollution degree
2
Surge voltage category
II
Housing material
PA 66-FR
Color
green
Name
Input/output/power supply
Electrical isolation
1.5 kV (50 Hz, 1 min., test voltage)