Datasheet
https://www.phoenixcontact.com/us/produkte/2865340
Nov 14, 20132/8
Power/input isolating amplifier-MACX MCR-EX-SL-RPSSI-
I-2865340
Technical data
Ambient conditions
Permissible humidity (operation)
10 % ... 95 % (no condensation)
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Degree of protection
IP20
Input data
Current input signal
0 mA ... 20 mA
Current input signal
4 mA ... 20 mA
Transmitter supply voltage
> 16 V (at 20 mA)
Voltage drop
< 3.5 V (in input isolating amplifier operation)
Output data
Signal output
Current output
Current output signal
0 mA ... 20 mA (active)
Current output signal
4 mA ... 20 mA (active)
Current output signal
0 mA ... 20 mA (14 ... 26 V ext. source voltage)
Current output signal
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Transmission Behavior
1:1 to input signal
Load/output load current output
< 600 Ω
Output ripple
< 20 mV
rms
Power supply
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC
Max. current consumption
< 60 mA (at 24 V DC)
Power consumption
< 1.1 W (at 24 V DC / 20 mA)
Connection data
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
14
Stripping length
7 mm
Screw thread
M3
Connection method
Screw connection
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
General
No. of channels
1
Maximum transmission error
< 0.1 % (of final value)