Datasheet

https://www.phoenixcontact.com/us/products/2865340
04/07/2017Page2/14
Power/input isolating amplifier-MACX MCR-EX-SL-RPSSI-I-2865340
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width 12.5 mm
Height 112.5 mm
Depth 114.5 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport) -40 °C ... 80 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Degree of protection IP20
Input data
Signal input Active current input, intrinsically safe
Current input signal 4 mA ... 20 mA
Transmitter supply voltage > 16 V (20 mA)
> 15.3 V (22.5 mA)
Polarization and surge protection Yes
Signal input Passive current input, intrinsically safe
Current input signal 0 mA ... 20 mA
4 mA ... 20 mA
Voltage drop < 3.5 V (in input isolating amplifier operation)
Output data
Signal output Current output (active and passive)
Current output signal 4 mA ... 20 mA (active)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Transmission Behavior 1:1 to input signal
Load/output load current output < 1000 Ω (20 mA)
< 825 Ω (24 mA)
Output ripple
< 20 mV
rms
Output behavior in the event of an error 0 mA (Cable break in the input)
≥ 22.5 mA (Cable short-circuit in the input)
Signal output Current output (active and passive)