Datasheet

https://www.phoenixcontact.com/us/produkte/2865007
Nov 13, 20133/9
Signal conditioner-MINI MCR-SL-U-UI-NC-2865007
Technical data
General
No. of channels
1
Maximum transmission error
< 0.1 % (of final value)
Maximum transmission error
< 0.4 % (Without adjustment)
Maximum temperature coefficient
< 0.01 %/K
Temperature coefficient, typical
< 0.002 %/K
Limit frequency (3 dB)
approx. 100 Hz
Step response (10-90%)
approx. 3.5 ms
Protective circuit
Transient protection
Electrical isolation
Basic insulation according to EN 61010
Surge voltage category
II
Pollution degree
2
Rated insulation voltage
50 V AC/DC
Test voltage, input/output/supply
1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Color
green
Housing material
PBT
Mounting position
Any
Assembly instructions
To bridge the supply voltage, the DIN rail connector (ME 6,2
TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used. It
can be snapped onto a 35 mm DIN rail according to EN 60715.
Conformance
CE-compliant
ATEX
 II 3 G Ex nA IIC T4 Gc X
UL, USA / Canada
UL 508 Recognized
UL, USA / Canada
Class I, Div. 2, Groups A, B, C, D T5
GL
GL EMC 2 D
EMC data
Name
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
5 %
Name
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
5 %
Name
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
5 %
classifications