Datasheet
https://www.phoenixcontact.com/us/produkte/2865007
Nov 13, 20132/9
Signal conditioner-MINI MCR-SL-U-UI-NC-2865007
Technical data
Ambient conditions
Degree of protection
IP20
Input data
Configurable/programmable
Yes, unconfigured
Voltage input signal
0 V ... 24 V
Voltage input signal
0 V ... 30 V
Max. input voltage
50 V DC
Input resistance of voltage input
approx. 125 kΩ (0 ... 24 V)
Input resistance of voltage input
approx. 155 kΩ (0 ... 30 V)
Output data
Configurable/programmable
Yes, unconfigured
Voltage output signal
0 V ... 10 V
Voltage output signal
0 V ... 5 V
Voltage output signal
1 V ... 5 V
Voltage output signal
2 V ... 10 V
Current output signal
0 mA ... 20 mA
Current output signal
4 mA ... 20 mA
Max. output voltage
≤ 12.5 V
Max. output current
28 mA
Short-circuit current
≤ 22 mA
Load/output load voltage output
> 10 kΩ
Load/output load current output
< 500 Ω (at 20 mA)
Power supply
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (The T connector (ME 6,2 TBUS-2 1,5/5-
ST-3,81 GN, Order No. 2869728) can be used to bridge the supply
voltage. It can be snapped onto a 35 mm DIN rail according to
EN60715))
Max. current consumption
< 19 mA (at 24 V DC incl. load)
Power consumption
< 450 mW
Connection data
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
26
Conductor cross section AWG/kcmil max
12
Stripping length
12 mm
Screw thread
M3
General