Datasheet

https://www.phoenixcontact.com/us/produkte/2864480
Nov 14, 20133/8
Limit value switches-MINI MCR-SL-UI-REL-2864480
Technical data
General
Electrical isolation
Basic insulation according to EN 61010
Surge voltage category
II
Pollution degree
2
Rated insulation voltage
50 V AC/DC
Test voltage input/power supply
1.5 kV AC (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Color
green
Housing material
PBT
Mounting position
Any
Assembly instructions
The T connector can be used to bridge the supply voltage. It can
be snapped onto a 35 mm DIN rail according to EN 60715.
Conformance
CE-compliant
ATEX
 II 3 G Ex nA nC IIC T4 Gc X
UL, USA
Class I, Zone 2, AEx nC IIC T6
UL, USA / Canada
UL 508 Recognized
UL, Canada
Class I, Zone 2, Ex nC IIC T6
GL
GL EMC 2 D
EMC data
Name
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
5 %
Name
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
5 %
Name
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
5 %
classifications
eCl@ss
eCl@ss 4.0
27210107
eCl@ss 4.1
27210107
eCl@ss 5.0
27210107
eCl@ss 5.1
27210107
eCl@ss 6.0
27210107
eCl@ss 7.0
27210107
eCl@ss 8.0
27210107