Datasheet

https://www.phoenixcontact.com/us/produkte/2864464
Nov 13, 20132/5
Current monitoring-MCR-SL-S- 16-SP- 24-2864464
Technical data
Input data
Nominal frequency f
N
50 Hz
Nominal frequency f
N
60 Hz
Frequency measuring range
45 Hz ... 65 Hz
Connection method
Through connection, diameter 4.2 mm
Switching output
Output name
Relay output
Contact type
1 PDT
Contact material
AgSnO, hard gold-plated
Maximum switching voltage
30 V AC
Maximum switching voltage
36 V DC
Maximum switching voltage
250 V AC
Limiting continuous current
50 mA (for gold layer, 30 V AC/ 36 V DC)
Limiting continuous current
2 A (in case of a destroyed gold layer, 250 V AC)
Setting range of the response delay
typ. 0.1 s ... 10 s (Adjustable using a potentiometer)
Power supply
Supply voltage range
20 V DC ... 30 V DC
Max. current consumption
< 30 mA
Connection data
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
14
Stripping length
8 mm
Screw thread
M3
General
Maximum temperature coefficient
< 0.02 %/K
Step response (10-90%)
40 ms
Surge voltage category
III
Pollution degree
2
Rated insulation voltage
300 V AC (to earth)
Test voltage input/output
4 kV (50 Hz, 1 min.)
Test voltage input/power supply
4 kV (50 Hz, 1 min.)
Color
green
Housing material
Polyamide PA non-reinforced
Mounting position
Any
Conformance
CE-compliant