Datasheet

https://www.phoenixcontact.com/us/produkte/2864406
Nov 13, 20132/8
Signal conditioner-MINI MCR-SL-I-I-2864406
Technical data
Input data
Configurable/programmable
No
Current input signal
0 mA ... 20 mA
Current input signal
4 mA ... 20 mA
Max. input current
50 mA
Input resistance current input
approx. 50 Ω
Output data
Configurable/programmable
No
Current output signal
0 mA ... 20 mA
Current output signal
4 mA ... 20 mA
Max. output current
28 mA
Load/output load current output
< 500 Ω (at 20 mA)
Power supply
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (The T connector (ME 6,2 TBUS-2 1,5/5-
ST-3,81 GN, Order No. 2869728) can be used to bridge the supply
voltage. It can be snapped onto a 35 mm DIN rail according to
EN60715))
Max. current consumption
< 20 mA
Power consumption
< 450 mW
Connection data
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
26
Conductor cross section AWG/kcmil max
12
Stripping length
12 mm
Screw thread
M3
General
No. of channels
1
Maximum transmission error
≤ 0.1 % (of final value)
Maximum temperature coefficient
< 0.01 %/K
Temperature coefficient, typical
< 0.002 %/K
Limit frequency (3 dB)
approx. 100 Hz
Step response (10-90%)
approx. 3.2 ms
Protective circuit
Transient protection
Electrical isolation
Basic insulation according to EN 61010
Surge voltage category
II
Pollution degree
2
Rated insulation voltage
50 V AC/DC