Datasheet

https://www.phoenixcontact.com/us/produkte/2864150
Nov 13, 20133/9
Signal conditioner-MINI MCR-SL-UI-UI-NC-2864150
Technical data
General
No. of channels
1
Maximum transmission error
≤ 0.1 % (of final value)
Maximum transmission error
< 0.4 % (Without adjustment)
Maximum temperature coefficient
< 0.01 %/K
Temperature coefficient, typical
< 0.002 %/K
Limit frequency (3 dB)
approx. 100 Hz
Step response (10-90%)
approx. 3.2 ms
Protective circuit
Transient protection
Electrical isolation
Basic insulation according to EN 61010
Surge voltage category
II
Pollution degree
2
Rated insulation voltage
50 V AC/DC
Test voltage, input/output/supply
1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Color
green
Housing material
PBT
Mounting position
Any
Assembly instructions
The T connector can be used to bridge the supply voltage. It can
be snapped onto a 35 mm DIN rail according to EN 60715.
Conformance
CE-compliant
ATEX
 II 3 G Ex nA IIC T4 Gc X
UL, USA / Canada
UL 508 Recognized
UL, USA / Canada
Class I, Div. 2, Groups A, B, C, D T5
GL
GL EMC 2 D
EMC data
Name
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
5 %
Name
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
5 %
Name
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
5 %
classifications
eCl@ss
eCl@ss 4.0
27210120