Datasheet

https://www.phoenixcontact.com/us/produkte/2814537
Nov 13, 20132/5
Signal conditioner-MCR-C-U-I- 4-DC-2814537
Technical data
Output data
Output name
Current output
Configurable/programmable
No
Current output signal
4 mA ... 20 mA
Max. output current
30 mA
Load/output load current output
≤ 500 Ω
Linear transmission range (in reference to the output range
end value)
-5 % ... 105 %
Power supply
Supply voltage range
20 V DC ... 30 V DC
Typical current consumption
< 15 mA (without load)
Connection data
Connection method
Pluggable screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
14
Stripping length
8 mm
Screw thread
M3
General
No. of channels
1
Maximum transmission error
≤ 0.3 % (of final value)
Transmission error, typical
< 0.2 % (of final value)
Maximum temperature coefficient
< 0.015 %/K
Limit frequency (3 dB)
30 Hz
Step response (10-90%)
11 ms
Protective circuit
Transient protection
Test voltage, input/output/supply
1.5 kV (50 Hz, 1 min.)
Color
green
Housing material
Polyamide PA non-reinforced
Mounting position
Any
Conformance
CE-compliant
classifications
eCl@ss
eCl@ss 4.0
27210120
eCl@ss 4.1
27210120
eCl@ss 5.0
27210120
eCl@ss 5.1
27210120