Datasheet

https://www.phoenixcontact.com/us/produkte/2814359
Nov 14, 20132/5
Current transducers-MCR-SLP-1-5-UI-0-2814359
Technical data
Input data
Power loss
1.6 VA (at I
A
= 20 mA)
Connection method
Screw connection
Input
Current measuring input 5 A
Input current range
0 A AC ... 0.005 A AC
Impulse form
Sine
Overload capacity
2 x I
N
(5 min. at 60°C ambient temperature)
Surge strength
100 A (1 s)
Permissible output range
1.2 x I
N
Nominal frequency f
N
50 Hz
Frequency measuring range
45 Hz ... 60 Hz
Power loss
2.2 VA (at I = 20 mA)
Connection method
Screw connection
Output data
Output name
Voltage output
Voltage output signal
0 V ... 10 V
Max. output voltage
20 V
Load/output load voltage output
> 100 kΩ
Output name
Current output
Current output signal
0 mA ... 20 mA
Max. output current
30 mA
Load/output load current output
< 750 Ω
Residual ripple, in reference to the measured value
0.5 % (pp of measured value)
Switching output
Output name
No switching output
Connection data
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
14
Stripping length
8 mm
Screw thread
M3
General
Maximum transmission error
< 0.5 % (of final value)
Maximum temperature coefficient
< 0.015 %/K
Step response (10-90%)
< 200 ms
Protective circuit
Transient protection in the output Suppressor diode